SPECIFICATIONS
Taps™ Odor Control VENT FILTERS
scope
1. 1 Under this
item, the contractor shall supply and install to
manufacturer's recommendations a Taps™ Vent Filter as
shown on contract drawings and specified hereunder.
MATERIALS & DESIGN
General
2.1 The Taps™ Vent Filter
and any associated components shall be manufactured from
corrosion - proof material suitable for atmospheres
containing hydrogen sulfide and dilute sulfuric acid as well as other gases
common to wastewater collection and processing, and be
filled with dry granules capable of effective control of
odors associated with such gases.
The Filter Body
2.2 The filter body and
related components such as reducers and flanges shall be
made of Schedule 40 PVC or of ABS plastic. The
perforated end caps shall be of polypropylene. Fasteners
shall be of 302 stainless steel.
The Filter
Granules
2.3 The granules shall
remove H
2S and malodorous compounds from the
air stream via dry-air oxidation chemistry. Oxidation
shall be accomplished via molecular contact with the
granules, producing solid by-products which are
deposited on and within the media. Other malodorous
gases shall be treated by absorption and adsorption.
Oxidation and absorptive capacities shall not be
diminished by ambient humidity.
Granule Replacement
2.4 The filter assembly shall be
refillable upon removal from vent stack.
INSTALLATION
3.1 Filter shall
push over vent stack or spigot x
socket reducing bushing to a seating ring and be tightened
to vent stack by stainless steel thumb screws.
FIELD TESTING & TRAINING
4.1 Measure
atmospheric H
2S in ppm emanating from vent before and after
installation of filter.
4.2 No
field training required.
|